Resetting the totalizers – Burkert Type 8619 User Manual
Page 90

88
Adjustmentandcommissioning
8.11.5. restore the factory calibration of the analogue inputs
Refer to chap. 8.9 to access Calibration menu.
Mx:Inputs
AI1/AI2
Factory calibr.
Calibration
8.11.6. resetting the totalizers
This function is available if the software option "FLOW" is activated. See chap. 8.10.4.
Refer to chap. 8.9 to access Calibration menu.
Calibration
DI1/2 Totalizer
Reset totalizer A
M0:Inputs
Reset totalizer B
Yes/No
Yes/No
Mx:Inputs
8.11.7. entering the K factor for the used fitting or determining it
using teach-in
This function is available on the devices with analysis modules if the software option, "FLOW", is activated. See
chap. 8.10.4.
Refer to chap. 8.9 to access Calibration menu.
Mx:Inputs
Calibration
DI1/2:Flow
M0:Inputs
Flow unit
Start teaching
Volume teaching
Flow teaching
Meas.in progr.
Flow teaching
Teaching result
L
m3
gal
Igal
Volume unit
Start teaching
Meas.in progr.
Flowed Volume
Teaching result
K factor
ENTERING
L/h
Igal/s
Flow unit
...
L/h
Igal/s
...
→
Use one of the following 3 methods to configure the pulse input of the multiCELL for a flow rate measurement:
•
K.FACTOR: Enter the K factor in pulse/liter unique to the fitting used. Refer to the user manual of the fitting
used.
Type 8619