Configuring a "prop" proportional function – Burkert Type 8619 User Manual
Page 48

46
Adjustmentandcommissioning
NAME: Rename the function chosen. See chap. 8.4. This name appears in the view associated with this function
in Process level.
STATUS: Used to activate (choose "ON") or deactivate (choose "OFF") the view of the function selected in
Process level.
PV A (or PV B): Combine a physical parameter (or the result of one of the functions, F1 to F6, already used) with
variable A (or B). Variables A and B must be of the same value type and have the same unit.
FILTER: Choose the level of damping of the input variables. See Figure 29.
0
13:40
0
0
MENU
F1:A+B
148
L/min
57
L/min
205
L/min
Value of variable A
Value of variable B
Result of the function A+B
2010/06/29
Figure 34 :
Example of a view of an active arithmetic function in Process level
8.10.12. configuring a "prop" proportional function
Configuring a "PROP" proportional function
0%
100%
"PROP" function
Process
input (PV)
fallback
position
System switch
Fx result: (CMD)
scale-
scale+
Figure 35 :
"PROP" proportional function
Refer to chap. 8.9 to access Parameters menu.
Type 8619