Adjustmentandcommissioning

PV: Choose the process input from the list displayed by the device. This value may be a measurement input or the
result of the function.
SP TYPE: Choose between an internal setpoint value (choose "internal") or an external setpoint value (choose
"external"; then select the parameter used as the setpoint from the list in the "SP-PV" function below).
SP-PV: Choose the parameter used as the external setpoint for the function.
PV RANGE: Enter the minimum ("PVRange-" ) and maximum ("PVRange+") measurement values of the process
input.
REG TYPE: Choose a linear control mode (choose "linear") or non-linear control mode (choose "non-linear"; then
enter under "Low" and "High" the 2 process input thresholds outside of which the "Drift" part is deactivated).

pH

"High" value

Reagent

"Low" value

Setpoint value

"PID" function

"PI" function (D = 0)

"PI" function (D = 0)

Figure 45 :

Example of non-linear control of the pH

CMD DIRECTION: Choose the control direction for the function (CMD1 or CMD2 respectively): ascending
(choose "Rise") or descending (choose "Fall").

0%

100%

100%

Fx / CMD

Output calculated by the function

Rise

Fall

Figure 46 :

CMD DIRECTION graphs

Type 8619

english