Burkert Type 8619 User Manual
Page 91
89
Adjustmentandcommissioning
•
VOLUME TEACH: Determine the K factor unique to your installation using a teach-in procedure by volume.
Follow the procedure below.
•
FLOW TEACH: Determine the K factor unique to your installation using a teach-in procedure by flow rate.
Follow the procedure on next page.
Detailed procedure for teach-in by volume
→
Prepare a tank capable of containing 100 litres, for example;
→
Choose the volume unit and the flow rate unit in which the teach-in is run:
Mx:Inputs
Calibration
DI1/2: Flow
M0:Inputs
Volume teaching
L
m3
gal
Igal
Volume unit
L/h
Igal/s
Flow unit
...
→
Running teach-in by volume:
→
Open the valve to fill the tank.
The multiCELL displays the K factor calculated
by teach-in.
OK
The multiCELL displays the
instantaneous flow rate of the fluid.
OK
→
When the tank is filled, close the valve.
OK
2.001 l/s
The multiCELL displays the
volume calculated with the
current K factor.
→
Enter the actual volume of fluid in
the tank.
101.2 l
+099.0 l
Volume teaching
Calibration
DI1:/DI2:Flow
M0:Inputs
Start teaching
Meas. in progr.
Flowed volume
Flow K factor:
K=3,810
Teaching result
Type 8619
english