beautypg.com

3 fuse specifications, 1 branch circuit protection fuses – Bell & Gossett P2001487 Technologic Pump Controller User Manual

Page 84

background image

10.3 Fuse

Specifications

10.3.1 Branch Circuit Protection Fuses

For compliance with IEC/EN 61800-5-1 electrical standards the following fuses are recommended.

Frequency

converter

Maximum fuse size

Voltage

Type

200-240 V - T2

1K1-1K5

16A

1

200-240

type gG

2K2

25A

1

200-240

type gG

3K0

25A

1

200-240

type gG

3K7

35A

1

200-240

type gG

5K5

50A

1

200-240

type gG

7K5

63A

1

200-240

type gG

11K

63A

1

200-240

type gG

15K

80A

1

200-240

type gG

18K5

125A

1

200-240

type gG

22K

125A

1

200-240

type gG

30K

160A

1

200-240

type gG

37K

200A

1

200-240

type aR

45K

250A

1

200-240

type aR

380-480 V - T4

1K1-1K5

10A

1

380-500

type gG

2K2-3K0

16A

1

380-500

type gG

4K0-5K5

25A

1

380-500

type gG

7K5

35A

1

380-500

type gG

11K-15K

63A

1

380-500

type gG

18K

63A

1

380-500

type gG

22K

63A

1

380-500

type gG

30K

80A

1

380-500

type gG

37K

100A

1

380-500

type gG

45K

125A

1

380-500

type gG

55K

160A

1

380-500

type gG

75K

250A

1

380-500

type aR

90K

250A

1

380-500

type aR

1) Max. fuses - see national/international regulations for selecting an applicable fuse size.

Table 10.14 EN50178 fuses 200 V to 480 V

Specifications

81

10