Inspect for

Description

Environmental consider-

ations

See equipment label for the maximum ambient operating temperature limits

Humidity levels must be 5-95% non-condensing

Fusing and circuit

breakers

Check for proper fusing or circuit breakers

Check that all fuses are inserted firmly and in operational condition and that all circuit breakers are

in the open position

Earthing (Grounding)

The unit requires an earth wire (ground wire) from its chassis to the building earth (ground)

Check for good earth connections (ground connections) that are tight and free of oxidation

Earthing (grounding) to conduit or mounting the back panel to a metal surface is not a suitable

earth (ground)

Input and output power

wiring

Check for loose connections

Check that motor and mains are in separate conduit or separated screened cables

Panel interior

Inspect that the unit interior is free of dirt, metal chips, moisture, and corrosion

Switches

Ensure that all switch and disconnect settings are in the proper positions

Vibration

Check that the unit is mounted solidly or that shock mounts are used, as necessary

Check for an unusual amount of vibration

Table 3.1 Start Up Check List