Bell & Gossett P2001487 Technologic Pump Controller User Manual
Page 38

1.
Press [Main Menu] twice, scroll to parameter
group 5-** Digital In/Out and press [OK].
Illustration 5.9 6-15 Terminal 53 High Ref./Feedb. Value
2.
Scroll to parameter group 5-1* Digital Inputs and
press [OK].
Illustration 5.10 Digital In/Out
3.
Scroll to 5-10 Terminal 18 Digital Input. Press [OK]
to access function choices. The default setting
Start is shown.
Illustration 5.11 Digital Inputs
5.4 International/North American Default
Parameter Settings
Setting 0-03 Regional Settings to [0] International or [1]
North America changes the default settings for some
parameters. Table 5.1 lists those parameters that are
effected.
Parameter
International
default parameter
value
North American
default parameter
value
0-03 Regional
Settings
International
North America
1-20 Motor Power
[kW]
See Note 1
See Note 1
1-21 Motor Power
[HP]
See Note 2
See Note 2
1-22 Motor Voltage
230 V/400 V/575 V
208 V/460 V/575 V
1-23 Motor
Frequency
50 Hz
60 Hz
3-03 Maximum
Reference
50 Hz
60 Hz
3-04 Reference
Function
Sum
External/Preset
4-13 Motor Speed
High Limit [RPM]
See Note 3 and 5
1500 PM
1800 RPM
4-14 Motor Speed
High Limit [Hz]
See Note 4
50 Hz
60 Hz
4-19 Max Output
Frequency
100 Hz
120 Hz
4-53 Warning Speed
High
1500 RPM
1800 RPM
5-12 Terminal 27
Digital Input
Coast inverse
External interlock
5-40 Function Relay Alarm
No alarm
6-15 Terminal 53
High Ref./Feedb.
Value
50
60
6-50 Terminal 42
Output
Speed 0-HighLim
Speed 4-20 mA
14-20 Reset Mode
Manual reset
Infinite auto reset
Table 5.1 International/North American Default Parameter
Settings
Note 1: 1-20 Motor Power [kW] is only visible when 0-03 Regional
Settings is set to [0] International.
Note 2: 1-21 Motor Power [HP], is only visible when 0-03 Regional
Settings is set to [1] North America.
Note 3: This parameter is only visible when 0-02 Motor Speed Unit is
set to [0] RPM.
Note 4: This parameter is only visible when 0-02 Motor Speed Unit is
set to [1] Hz.