1.

Press [Main Menu] twice, scroll to parameter
group 5-** Digital In/Out and press [OK].

Illustration 5.9 6-15 Terminal 53 High Ref./Feedb. Value

2.

Scroll to parameter group 5-1* Digital Inputs and
press [OK].

Illustration 5.10 Digital In/Out

3.

Scroll to 5-10 Terminal 18 Digital Input. Press [OK]
to access function choices. The default setting
Start is shown.

Illustration 5.11 Digital Inputs

5.4 International/North American Default

Parameter Settings

Setting 0-03 Regional Settings to [0] International or [1]
North America
changes the default settings for some
parameters. Table 5.1 lists those parameters that are
effected.

Parameter

International

default parameter

value

North American

default parameter

value

0-03 Regional

Settings

International

North America

1-20 Motor Power

[kW]

See Note 1

See Note 1

1-21 Motor Power

[HP]

See Note 2

See Note 2

1-22 Motor Voltage

230 V/400 V/575 V

208 V/460 V/575 V

1-23 Motor

Frequency

50 Hz

60 Hz

3-03 Maximum

Reference

50 Hz

60 Hz

3-04 Reference

Function

Sum

External/Preset

4-13 Motor Speed

High Limit [RPM]

See Note 3 and 5

1500 PM

1800 RPM

4-14 Motor Speed

High Limit [Hz]

See Note 4

50 Hz

60 Hz

4-19 Max Output

Frequency

100 Hz

120 Hz

4-53 Warning Speed

High

1500 RPM

1800 RPM

5-12 Terminal 27

Digital Input

Coast inverse

External interlock

5-40 Function Relay Alarm

No alarm

6-15 Terminal 53

High Ref./Feedb.

Value

50

60

6-50 Terminal 42

Output

Speed 0-HighLim

Speed 4-20 mA

14-20 Reset Mode

Manual reset

Infinite auto reset

Table 5.1 International/North American Default Parameter

Settings

Note 1: 1-20 Motor Power [kW] is only visible when 0-03 Regional

Settings is set to [0] International.

Note 2: 1-21 Motor Power [HP], is only visible when 0-03 Regional

Settings is set to [1] North America.

Note 3: This parameter is only visible when 0-02 Motor Speed Unit is

set to [0] RPM.

Note 4: This parameter is only visible when 0-02 Motor Speed Unit is

set to [1] Hz.