2 general technical data – Bell & Gossett P2001487 Technologic Pump Controller User Manual
Page 79

10.2 General Technical Data
Mains supply
Supply Terminals
L1, L2, L3
Supply voltage
200-240 V
±10%
Supply voltage
380-480 V/525-600 V
±10%
Supply voltage
525-690 V
±10%
Mains voltage low/mains drop-out:
During low mains voltage or a mains drop-out, the drive continues until the intermediate circuit voltage drops below the
minimum stop level, which corresponds typically to 15% below the frequency converter's lowest rated supply voltage. Power-up
and full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest rated supply
voltage.
Supply frequency
50/60 Hz
±5%
Max. imbalance temporary between mains phases
3.0 % of rated supply voltage
True Power Factor (
λ)
≥ 0.9 nominal at rated load
Displacement Power Factor (cos
ϕ)
near unity (
> 0.98)
Switching on input supply L1, L2, L3 (power-ups)
≤ 7.5 kW
maximum 2 times/min.
Switching on input supply L1, L2, L3 (power-ups) 11-75 kW
maximum 1 time/min.
Switching on input supply L1, L2, L3 (power-ups)
≥ 90 kW
maximum 1 time/2 min.
Environment according to EN60664-1
overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240/500/600/690
V maximum.
Motor output (U, V, W)
Output voltage
0 - 100% of supply voltage
Output frequency (1.1-90 kW)
0-590 Hz
Output frequency (110-250 kW)
0-590
1)
Hz
Switching on output
Unlimited
Ramp times
1-3600 s
1)
Voltage and power dependent
Torque characteristics
Starting torque (Constant torque)
maximum 110% for 60 s
1)
Starting torque
maximum 135% up to 0.5 s
1)
Overload torque (Constant torque)
maximum 110% for 60 s
1)
Starting torque (Variable torque)
maximum 110% for 60 s
1)
Overload torque (Variable torque)
maximum 110% for 60 s
Torque rise time in VVC
plus
(independent of fsw)
10 ms
1)
Percentage relates to the nominal torque.
2)
The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4-5 x
torque rise time.
Cable lengths and cross sections for control cables
1)
Max. motor cable length, screened
150 m
Max. motor cable length, unscreened
300 m
Maximum cross section to control terminals, flexible/ rigid wire without cable end sleeves
1.5 mm
2
/16 AWG
Maximum cross section to control terminals, flexible wire with cable end sleeves
1 mm
2
/18 AWG
Maximum cross section to control terminals, flexible wire with cable end sleeves with collar
0.5 mm
2
/20 AWG
Minimum cross section to control terminals
0.25 mm
2
/24AWG
1)
For power cables, see electrical data tables.
Specifications
76
10
0