10.2 General Technical Data

Mains supply
Supply Terminals

L1, L2, L3

Supply voltage

200-240 V

±10%

Supply voltage

380-480 V/525-600 V

±10%

Supply voltage

525-690 V

±10%

Mains voltage low/mains drop-out:
During low mains voltage or a mains drop-out, the drive continues until the intermediate circuit voltage drops below the
minimum stop level, which corresponds typically to 15% below the frequency converter's lowest rated supply voltage. Power-up
and full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest rated supply
voltage.

Supply frequency

50/60 Hz

±5%

Max. imbalance temporary between mains phases

3.0 % of rated supply voltage

True Power Factor (

λ)

≥ 0.9 nominal at rated load

Displacement Power Factor (cos

ϕ)

near unity (

> 0.98)

Switching on input supply L1, L2, L3 (power-ups)

≤ 7.5 kW

maximum 2 times/min.

Switching on input supply L1, L2, L3 (power-ups) 11-75 kW

maximum 1 time/min.

Switching on input supply L1, L2, L3 (power-ups)

≥ 90 kW

maximum 1 time/2 min.

Environment according to EN60664-1

overvoltage category III/pollution degree 2

The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240/500/600/690
V maximum.

Motor output (U, V, W)
Output voltage

0 - 100% of supply voltage

Output frequency (1.1-90 kW)

0-590 Hz

Output frequency (110-250 kW)

0-590

1)

Hz

Switching on output

Unlimited

Ramp times

1-3600 s

1)

Voltage and power dependent

Torque characteristics

Starting torque (Constant torque)

maximum 110% for 60 s

1)

Starting torque

maximum 135% up to 0.5 s

1)

Overload torque (Constant torque)

maximum 110% for 60 s

1)

Starting torque (Variable torque)

maximum 110% for 60 s

1)

Overload torque (Variable torque)

maximum 110% for 60 s

Torque rise time in VVC

plus

(independent of fsw)

10 ms

1)

Percentage relates to the nominal torque.

2)

The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4-5 x

torque rise time.

Cable lengths and cross sections for control cables

1)

Max. motor cable length, screened

150 m

Max. motor cable length, unscreened

300 m

Maximum cross section to control terminals, flexible/ rigid wire without cable end sleeves

1.5 mm

2

/16 AWG

Maximum cross section to control terminals, flexible wire with cable end sleeves

1 mm

2

/18 AWG

Maximum cross section to control terminals, flexible wire with cable end sleeves with collar

0.5 mm

2

/20 AWG

Minimum cross section to control terminals

0.25 mm

2

/24AWG

1)

For power cables, see electrical data tables.

Specifications