1 uploading data to the lcp, 2 downloading data from the lcp, 3 restoring default settings – Bell & Gossett P2001487 Technologic Pump Controller User Manual
Page 35: 1 recommended initialisation, 2 manual initialisation, Warning, Caution

WARNING
UNINTENDED START!
When the frequency converter is connected to AC mains,
the motor may start at any time. The frequency
converter, motor, and any driven equipment must be in
operational readiness. Failure to be in operational
readiness when the frequency converter is connected to
AC mains could result in death, serious injury, or
equipment or property damage.
4.2.1 Uploading Data to the LCP
1.
Press [Off] to stop the motor before uploading or
downloading data.
2.
Go to 0-50 LCP Copy.
3.
Press [OK].
4.
Select All to LCP.
5.
Press [OK]. A progress bar shows the uploading
process.
6.
Press [Hand On] or [Auto On] to return to normal
operation.
4.2.2 Downloading Data from the LCP
1.
Press [Off] to stop the motor before uploading or
downloading data.
2.
Go to 0-50 LCP Copy.
3.
Press [OK].
4.
Select All from LCP.
5.
Press [OK]. A progress bar shows the
downloading process.
6.
Press [Hand On] or [Auto On] to return to normal
operation.
4.3 Restoring Default Settings
CAUTION
Initialisation restores the unit to factory default settings.
Any programming, motor data, localization, and
monitoring records will be lost. Uploading data to the
LCP provides a backup before initialisation.
Restoring the frequency converter parameter settings back
to default values is done by initialisation of the frequency
converter. Initialisation can be carried out through
14-22 Operation Mode or manually.
•
Initialisation using 14-22 Operation Mode does not
change frequency converter data such as
operating hours, serial communication selections,
personal menu settings, fault log, alarm log, and
other monitoring functions
•
Using 14-22 Operation Mode is generally
recommended
•
Manual initialisation erases all motor,
programming, localization, and monitoring data
and restores factory default settings
4.3.1 Recommended Initialisation
1.
Press [Main Menu] twice to access parameters.
2.
Scroll to 14-22 Operation Mode.
3.
Press [OK].
4.
Scroll to Initialisation.
5.
Press [OK].
6.
Remove power to the unit and wait for the
display to turn off.
7.
Apply power to the unit.
Default parameter settings are restored during start up.
This may take slightly longer than normal.
8.
Alarm 80 is displayed.
9.
Press [Reset] to return to operation mode.
4.3.2 Manual Initialisation
1.
Remove power to the unit and wait for the
display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at
the same time and apply power to the unit.
Factory default parameter settings are restored during start
up. This may take slightly longer than normal.
Manual initialisation does not reset the following frequency
converter information
•
15-00 Operating hours
•
15-03 Power Up's
•
15-04 Over Temp's
•
15-05 Over Volt's
User Interface
32
4
4