Mains supply 200-240 V AC - Normal overload 110% for 1 minute
Frequency converter
Typical Shaft Output [kW]
P1K1
1.1
P1K5
1.5
P2K2
2.2
P3K0
3
P3K7
3.7
IP20/Chassis
5)
A2
A2
A2
A3
A3
IP55/Type 12
A4/A5
A4/A5
A4/A5
A5
A5
IP66/NEMA 4X
A4/A5
A4/A5
A4/A5
A5
A5
Typical Shaft Output [HP] at 208 V
1.5
2.0
2.9
4.0
4.9
Output current
Continuous (3 x 200-240 V) [A]
6.6
7.5
10.6
12.5
16.7
Intermittent (3 x 200-240 V) [A]
7.3
8.3
11.7
13.8
18.4
Continuous kVA (208 V AC) [kVA]
2.38
2.70
3.82
4.50
6.00
Max. input current
Continuous (3 x 200-240 V) [A]
5.9
6.8
9.5
11.3
15.0
Intermittent (3 x 200-240 V) [A]
6.5
7.5
10.5
12.4
16.5
Additional specifications
Estimated power loss at rated max. load [W]
4)
63
82
116
155
185
IP20, IP21 max. cable cross section (mains, motor, brake and load sharing) [mm
2
/
(AWG)]
4, 4, 4 (12, 12, 12)
(min. 0.2 (24))
IP55, IP66 max. cable cross section (mains, motor, brake and load sharing) [mm
2
/
(AWG)]
4, 4, 4 (12, 12, 12)
Max. cable cross section with disconnect
6, 4, 4 (10, 12, 12)
Weight enclosure IP20 [kg]
4.9
4.9
4.9
6.6
6.6
Weight enclosure IP21 [kg]
5.5
5.5
5.5
7.5
7.5
Weight enclosure IP55 [kg] (A4/A5)
9.7/13.5
9.7/13.5
9.7/13.5
13.5
13.5
Weight enclosure IP66 [kg] (A4/A5)
9.7/13.5
9.7/13.5
9.7/13.5
13.5
13.5
Efficiency
3)
0.96
0.96
0.96
0.96
0.96
Table 10.2 Mains Supply 200-240 V AC