Symptom

Possible cause

Test

Solution

Acoustic noise or vibration

(e.g. a fan blade is making

noise or vibrations at

certain frequencies)

Resonances, e.g. in the motor/fan

system

Bypass critical frequencies by using

parameters in parameter group

4-6* Speed Bypass

Check if noise and/or vibration

have been reduced to an

acceptable limit

Turn off over-modulation in

14-03 Overmodulation

Change switching pattern and

frequency in parameter group

14-0* Inverter Switching

Increase Resonance Dampening in

1-64 Resonance Dampening

Table 9.1 Troubleshooting