beautypg.com

Bell & Gossett P2001487 Technologic Pump Controller User Manual

Page 73

background image

Mains Supply 3 x 380-480 V AC - Normal overload 110% for 1 minute

Frequency converter

Typical Shaft Output [kW]

P37K

37

P45K

45

P55K

55

P75K

75

P90K

90

Typical Shaft Output [HP] at 460 V

50

60

75

100

125

IP20/Chassis

6)

B4

C3

C3

C4

C4

IP21/NEMA 1

C1

C1

C1

C2

C2

IP55/Type 12

C1

C1

C1

C2

C2

IP66/NEMA 4X

C1

C1

C1

C2

C2

Output current

Continuous (3 x 380-439 V) [A]

73

90

106

147

177

Intermittent (3 x 380-439 V) [A]

80.3

99

117

162

195

Continuous (3 x 440-480 V) [A]

65

80

105

130

160

Intermittent (3 x 440-480 V) [A]

71.5

88

116

143

176

Continuous kVA (400 V AC) [kVA]

50.6

62.4

73.4

102

123

Continuous kVA 460 V AC) [kVA]

51.8

63.7

83.7

104

128

Max. input current

Continuous (3 x 380-439 V) [A]

66

82

96

133

161

Intermittent (3 x 380-439 V) [A]

72.6

90.2

106

146

177

Continuous (3 x 440-480 V) [A]

59

73

95

118

145

Intermittent (3 x 440-480 V) [A]

64.9

80.3

105

130

160

Additional specifications

Estimated power lossat rated max. load [W]

4)

739

843

1083

1384

1474

IP20 max. cable cross-section (mains, brake, motor and load sharing)

50 (1)

150 (300 MCM)

IP21, IP55, IP66 max. cable cross-section (mains, motor) [mm

2

/(AWG)]

150

(300

MCM)

IP21, IP55, IP66 max. cable cross-section (brake, load sharing) [mm

2

/

(AWG)]

95

(3/0)

With mains disconnect switch included:

35/2

35/2

70/3/0

185/

kcmil350

Weight enclosure IP20 [kg]

23.5

35

35

50

50

Weight enclosure IP21 [kg]

45

45

45

65

65

Weight enclosure IP55 [kg]

45

45

45

65

65

Weight enclosure IP66 [kg]

45

45

45

65

65

Efficiency

3)

0.98

0.98

0.98

0.98

0.99

Table 10.8 Mains Supply 3 x 380-480 V AC

Specifications

70

10

0