10.1.3 Mains Supply 3 x 525-690 V AC

Normal overload 110% for 1 minute

Frequency Converter

Typical Shaft Output [kW]

P1K1

1.1

P1K5

1.5

P2K2

2.2

P3K0

3

P4K0

4

P5K5

5.5

P7K5

7.5

Enclosure IP20 (only)

A3

A3

A3

A3

A3

A3

A3

Output current

Continuous (3x525-550 V) [A]

2.1

2.7

3.9

4.9

6.1

9

11

Intermittent (3x525-550 V) [A]

2.3

3.0

4.3

5.4

6.7

9.9

12.1

Continuous kVA (3x551-690 V) [A]

1.6

2.2

3.2

4.5

5.5

7.5

10

Intermittent kVA (3x551-690 V) [A]

1.8

2.4

3.5

4.9

6.0

8.2

11

Continuous kVA 525 V AC

1.9

2.6

3.8

5.4

6.6

9

12

Continuous kVA 690 V AC

1.9

2.6

3.8

5.4

6.6

9

12

Max. input current

Continuous (3x525-550 V) [A]

1.9

2.4

3.5

4.4

5.5

8

10

Intermittent (3x525-550 V) [A]

2.1

2.6

3.8

8.4

6.0

8.8

11

Continuous kVA (3x551-690 V) [A]

1.4

2.0

2.9

4.0

4.9

6.7

9

Intermittent kVA (3x551-690 V) [A]

1.5

2.2

3.2

4.4

5.4

7.4

9.9

Additional specifications

IP20 max. cable cross section

5)

(mains, motor,

brake and load sharing) [mm

2

]/(AWG)

[0.2-4]/(24-10)

Estimated power loss at rated max. load [W]

4)

44

60

88

120

160

220

300

Weight, enclosure IP20 [kg]

6.6

6.6

6.6

6.6

6.6

6.6

6.6

Efficiency

4)

0.96

0.96

0.96

0.96

0.96

0.96

0.96

Table 10.11 Mains Supply 3 x 525-690 V AC