beautypg.com

Bell & Gossett P2001487 Technologic Pump Controller User Manual

Page 69

background image

Mains Supply 3x200-240 V AC - Normal overload 110% for 1 minute

IP20/Chassis

6)

C3

C3

C4

C4

IP21/NEMA 1

C1

C1

C2

C2

IP55/Type 12

C1

C1

C2

C2

IP66/NEMA 4X

C1

C1

C2

C2

Frequency converter

Typical Shaft Output [kW]

P22K

22

P30K

30

P37K

37

P45K

45

Typical Shaft Output [HP] at 208 V

30

40

50

60

Output current

Continuous (3 x 200-240 V) [A]

88.0

115

143

170

Intermittent (3 x 200-240 V) [A]

96.8

127

157

187

Continuous kVA (208 V AC) [kVA]

31.7

41.4

51.5

61.2

Max. input current

Continuous (3 x 200-240 V) [A]

80.0

104.0

130.0

154.0

Intermittent (3 x 200-240 V) [A]

88.0

114.0

143.0

169.0

Additional Specifications

Estimated power loss at rated max. load [W]

4)

845

1140

1353

1636

IP20 max. cable cross-section (mains, brake, motor and load sharing)

150 (300 MCM)

IP21, IP55, IP66 max. cable cross-section (mains, motor) [mm

2

/AWG]

150

(300

MCM)

IP21, IP55, IP66 max. cable cross-section (brake, load sharing) [mm

2

/AWG]

95 (3/0)

Weight enclosure IP20 [kg]

35

35

50

50

Weight enclosure IP21 [kg]

45

45

65

65

Weight enclosure IP55 [kg]

45

45

65

65

Weight enclosure IP66 [kg]

45

45

65

65

Efficiency

3)

0.97

0.97

0.97

0.97

Table 10.4 Mains Supply 3x200-240 V AC

Specifications

66

10

0