48 vdc redundant source power supply pinouts, Installing the redundant – 48 vdc power supply – Paradyne ACCULINK 316x User Manual

Page 31

background image

ACCULINK 316x DSU/CSU

2-8

December 1996

3160-A2-GB22-10

Installing the Redundant –

ā

48 Vdc Power

Supply

To install the 3160/3164 DSU/CSU using a redundant

– 48 Vdc power supply, refer to Figure 2-9 and use the
following procedure.

To install the redundant –48 Vdc power supply,

1. Connect the black wire to the –48 Vdc return

source B.

2. Connect the red wire to the –48 Vdc return

source A.

3. Connect the green wire to a suitable earth ground.

4. Connect the orange wire to the –48 Vdc input

source B.

5. Connect the blue wire to the –48 Vdc input

source A.

6. Cut the white wire off at the outer insulation.

7. Plug the power connector into the 3160/3164

DSU/CSU.

Figure 2-9. –

ā

48 Vdc Redundant Source Power Supply Pinouts