B,)-Set VOM to ”+DC” and to any

scale that will permit 12 Volts

to be read. Connect the positi­
ve meter test probe to the Wire

No. 4 connection at Field Boost

Module, Connect the common (-)

test probe to frame ground. De­

press the Fuel Pump button- the

meter should indicate 9-12 Volts

DC.

RESULT;-No voltage indicated........................Go to Paragraph C

Voltage is indicated, but none .... .Repair/replace Wire No. 4

in Paragraph A

between red receptacle and Field

Boost Module

C,)-Set VOM to ”+DC” and to any scale that will permit 12 Volts DC to

be read. Connect the positive (+) meter test probe to the Wire No. 14

connection at Field Boost Module, Connect the common (-) test probe
to frame ground. Depress the Fuel Pump button. Meter needle should ift-
dicate 9-12 Volts DC.

RESULT:-Normal DC voltage indicated....... Replace Field Boost Module

but not in Paragraph B

No voltage indicated.... ..... .Check Wire No. 14 between

the Field Boost Module and the

Control Relay (CR)

2.4-7