B,)-Set VOM to ”+DC” and to any
scale that will permit 12 Volts
to be read. Connect the positi
ve meter test probe to the Wire
No. 4 connection at Field Boost
Module, Connect the common (-)
test probe to frame ground. De
press the Fuel Pump button- the
meter should indicate 9-12 Volts
DC.
RESULT;-No voltage indicated........................Go to Paragraph C
Voltage is indicated, but none .... .Repair/replace Wire No. 4
in Paragraph A
between red receptacle and Field
Boost Module
C,)-Set VOM to ”+DC” and to any scale that will permit 12 Volts DC to
be read. Connect the positive (+) meter test probe to the Wire No. 14
connection at Field Boost Module, Connect the common (-) test probe
to frame ground. Depress the Fuel Pump button. Meter needle should ift-
dicate 9-12 Volts DC.
RESULT:-Normal DC voltage indicated....... Replace Field Boost Module
but not in Paragraph B
No voltage indicated.... ..... .Check Wire No. 14 between
the Field Boost Module and the
Control Relay (CR)
2.4-7