beautypg.com

Generac Power Systems MC User Manual

Page 42

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

RESULT:- Primary windiag rasistance. checks good..Check customer wiring

Primary winding resistance is bad,.......Replace Transformer

NOTE

The Sensing Transformer secondary windings MUST connect to the
Voltage Regulator, The primary windings..must connect to the
white connector plug. In most cases, primary and secondary wi­
ndings will be identified when replacing a Transformer. If the

windings are not identified, check winding resistance. The
winding having the HIGHEST resistance is the SECONDARY winding.

TEST 38:- MAIN CIRCUIT BREAKER

Set VOM to ”+DC" and to "Rxl" scale.
Zero the meter. See illustration at

right. Connect VOM test probes acr­
oss the Main Rreaker teat points.

Meter needle should swing upscale to

zero with Main Breaker ON, When the

Breaker is set .to OFF, needle should

drop all the way downscale (infinity),

RESULT:- Main Breaker cheeks good.

Main Breaker feeafes bad.

.Continue diagnostic tests
..........Replace Breaker

TEST 39:- CHECK ROTOR

A.)-Disconnect the white connect­

or plug from its receptacle on the
stator can. Set VOM to "+DC” and
to "Rxl” scale, then zero the met­
er. Connect the positive (+) meter

test probe to white receptacle Pin
4, Connect the common (-) probe to
receptacle Pin 1, Meter needle
should swing upscale and indicate
rotor winding resistance (approxi­

mately 15,6 Ohms),

RESULT:- Rotor checks good

Rotor checks bad..

.... Go to Test 40
,Go to Paragraph B

2.2-20