D.)-Set VOM to ”+DC'’ and to ”50V.”

scale. Connect the positive (+)

meter test probe to the Wire No. 91

terminal on the choke solenoid and

the remaining test probe to frame
ground. Crank the engine - meter

needle should swing upscale and in­

dicate a steady 12 Volts DC.

RESULTS:- Meter does not indicate IZ Volts....Check Wire No. 91 for an

open or shorted condition

Meter indicates 12 Volts DC................Go to Paragraph E

E.)- Set VOM to "+DC” and to ”50V.'' scale. Connect the positive ( + ) me­
ter test probe to the Wire No. 90 terminal on the choke solenoid and

the common (-) test probe to frame ground. Crank the engine - meter nee­
dle should indicate a pulsing voltage as choke pulses open and closed.

RESULTS:- No meter needle movement......Replace Printed Circuit Board

(Model 6897-4:-Replace Choke

Pulse Module [CM]. See Sect-

jL

2 ^ )

Meter test is good but choke

does not actuate.....................Replace Choke assembly

TEST 31:- PRE-CHOKE

With the choke Bi-Metal at ambient

temperature, the carburetor choke

plate should be approximately 1/8

inch away from its full open posi­
tion (toward the closed position).

If necessary, loosen the bi-metal

adjusting screws and move the bi­

metal to obtain this setting. This

is the "Pre-Choke" position.

2.2-16