Genesis II Installation Instructions
© Mass Electronics Pty Ltd 2010
Chapter 4 – Commissioning
4-1.4 Set Jumper Plugs
Various jumper plugs throughout the system must be set properly before power can be applied to the
system.
There are 4 categories of jumper plug:
Address Plugs set the address of each Remote Expansion Module
• Analogue Output plugs are used to select either Variable or Heat Valve Mode of operation for
analogue outputs. Refer to section
for a definition of Variable and Heat Valve Modes.
• End-of-Cable jumpers provide the proper termination impedance for the RS485 Comms Cable. It is
installed in the last unit of the cable run
• Frequency Plugs set the frequency of each wireless Remote Expansion Module or Interface
The computer-generated wiring diagram (
) shows the locations and required settings for
each address jumper and analogue output jumper.
Table 4-4 is provided as an aid for properly setting the various jumper plugs. The table lists
the required jumper setting, the types of jumper plugs and the reference paragraph containing
instructions for setting them for each Genesis II unit.
Terminal
Address
End of Cable
Analogue Output
Frequency
See Paragraph:
GENII DDC Digital
Controller
Yes
MPCII Mid Points
Controller
Yes
GENII AI REM
Yes
Yes
GENII AO REM
Yes
Yes
Yes
GENII DI REM
Yes
Yes
GENII DO REM
Yes
Yes
GENII IDI REM
Yes
Yes
GENII PI REM
Yes
Yes
GENII MZS REM
Yes
Yes
GENII MZSAH REM
Yes
Yes
GENII CS REM
Yes
Yes
GENII CSAH REM
Yes
Yes
GENII CSFCAH REM
Yes
Yes
GENII MP REM
Yes
GENII MP405 REM
Yes
GENII MP414 REM
Yes
GENII MP423 REM
Yes
GENII MP432 REM
Yes
GENII WMI
Yes
SENRx
Yes
Yes
Table 4-4:
Units Requiring Jumper Settings