Chapter 2 – Mechanical Installation
2-2.2.4 REM Multipoint Modules
REM Multipoint Modules provide additional Analogue/Digital output capabilities for a Genesis II Series
digital controller.
There are a total of three different REM Multipoint Modules.
• GENII MP405 REM Multipoint Module
• GENII MP423 REM Multipoint Module
• GENII MP432 REM Multipoint Module
Common Enclosure Information
The above listed REM Multipoint Modules are housed in a rectangular case suitable for DIN Rail
mounting. The housing is moulded from flame retardant plastics recognised by UL as UL 94-V0.
Colour:
Grey
Dimensions(max):
107mm(w) x 100mm(h) x 65mm(d)
Mounting:
DIN Rail Mounted
The cable run between a digital controller and REM Multipoint Modules should not exceed 600
metres. However, the maximum cable length can be increased through the use of Innotech Repeater
IR11 module. Refer to Paragraph
for more information.
Below is a schematic of the GENII MP405 REM Multi Zone Station Module. The above listed REM
Multipoint Modules feature the same dimensions and similar appearance. Refer to Figure 2-7.
107
36
DI
4
DI
1
DI
2
DI
3
+
-
Comms
Jumpers
A2
A1
A0
EOL
SHLD
2
SHLD
1
TH2
TH1
+
-
+
-
+
-
+
-
Co m
NO
DO 1
DO 2
DO 3
0 V
24V
Co m
NO
Co m
NO
+
AO
-
1
+
AO
-
2
E
7
90
50
36
65
12
100
Figure 2-7: GenII MP405 REM Multipoint Module