beautypg.com

Genii mp405 rem multipoint module – Innotech Genesis II Digital Controller (v5) User Manual

Page 23

background image

Page 23

Genesis II Installation Instructions

© Mass Electronics Pty Ltd 2010

Chapter 2 – Mechanical Installation

2-2.2.4 REM Multipoint Modules

REM Multipoint Modules provide additional Analogue/Digital output capabilities for a Genesis II Series

digital controller.

There are a total of three different REM Multipoint Modules.

• GENII MP405 REM Multipoint Module

• GENII MP423 REM Multipoint Module

• GENII MP432 REM Multipoint Module

Common Enclosure Information

The above listed REM Multipoint Modules are housed in a rectangular case suitable for DIN Rail

mounting. The housing is moulded from flame retardant plastics recognised by UL as UL 94-V0.

Colour:

Grey

Dimensions(max):

107mm(w) x 100mm(h) x 65mm(d)

Mounting:

DIN Rail Mounted

The cable run between a digital controller and REM Multipoint Modules should not exceed 600

metres. However, the maximum cable length can be increased through the use of Innotech Repeater

IR11 module. Refer to Paragraph

5-3.3.3

for more information.

Below is a schematic of the GENII MP405 REM Multi Zone Station Module. The above listed REM

Multipoint Modules feature the same dimensions and similar appearance. Refer to Figure 2-7.

107

36

DI

4

DI

1

DI

2

DI

3

+

-

Comms

Jumpers

A2

A1

A0

EOL

SHLD

2

SHLD

1

TH2

TH1

+

-

+

-

+

-

+

-

Co m

NO

DO 1

DO 2

DO 3

0 V

24V

Co m

NO

Co m

NO

+

AO

-

1

+

AO

-

2

E

7

90

50

36

65

12

100

Figure 2-7:  GenII MP405 REM Multipoint Module