Genesis ii ddc output signal conditions – Innotech Genesis II Digital Controller (v5) User Manual
Page 38

Genesis II Installation Instructions
Page 38
© Mass Electronics Pty Ltd 2010
Edition 2.0 dated 06/12/2013
3-3.1.3 Digital Outputs
Each of the Genesis II Direct Digital Controller’s twelve digital output channels (Terminals 42–65)
consists of a single-pole, double-throw (SPDT) relay. The two terminals assigned to each channel
represent the associated relay’s Normally Open (NO) and Common (COM) contacts.
Digital output relay contacts are rated at 24VAC, 2A. Good practice is to use pilot relays for the actual
switching functions, particularly when it applies to inductive loads such as coils, solenoids and
motors. This protects the relays of the Digital Output channel and has the advantage of allowing the
pilot relays to be installed adjacent to the controlling switch-gear.
Refer to Table 3-4 for Digital Output terminal number assignments.
Normally Open (NO)
Common (COM)
Terminal
Signal
Terminal
Signal
42
DO 1 NO
43
DO 1 COM
44
DO 2 NO
45
DO 2 COM
46
DO 3 NO
47
DO 3 COM
48
DO 4 NO
49
DO 4 COM
50
DO 5 NO
51
DO 5 COM
52
DO 6 NO
53
DO 6 COM
54
DO 7 NO
55
DO 7 COM
56
DO 8 NO
57
DO 8 COM
58
DO 9 NO
59
DO 9 COM
60
DO 10 NO
61
DO 10 COM
62
DO 11 NO
63
DO 11 COM
64
DO 12 NO
65
DO 12 COM
Table 3-4:
Genesis II DDC Output Signal Conditions