3.2 general installation instructions, Genesis ii ddc optimum display viewing angle, E 2-12 – Innotech Genesis II Digital Controller (v5) User Manual

Page 28

background image

Genesis II Installation Instructions

Page 28

© Mass Electronics Pty Ltd 2010

Edition 2.0 dated 06/12/2013

Side View

Top View

90 Degrees

45

Degrees

2-3.2 General Installation Instructions

To ensure continued reliable operation of the Genesis II System, the following installation guidelines

should be observed:

• The Genesis II Direct Digital Controller or MPCII Mid Points Controller should be installed in a

position that provides easy access to the front panel and sufficient room for power, and input/

output cabling. Also, the Digital Controller should be mounted such that the controls are in easy

reach of the user. This requirement does not apply to the MPCII Mid Points Controller which has no

external controls or indicators.

• Placement of the Genesis II Direct Digital Controller should take into account the

optimum

viewing angle of the Liquid Crystal Display (LCD), which is approximately 45° vertically and 90°

horizontally (see Figure 2-12).

• Do not mount any unit of the system near high voltage, high current cables or sources of strong

radio frequency emissions such as transmitter antenna cables.

• The ambient temperature of the digital controller and REMs at the installation site should not

exceed the 0-40 °C temperature range.

• Mount the units in an area with minimum vibration and minimum exposure to mechanical

damage.

• The REMs must be installed within 600 metres of the Genesis II Direct Digital Controller or MPCII

Mid Points Controller.