4.9 genii mzs rem multi zone station module, Genii mzs rem multizone station module, E 3-13 – Innotech Genesis II Digital Controller (v5) User Manual
Page 59

Page 59
Genesis II Installation Instructions
© Mass Electronics Pty Ltd 2010
Chapter 3 – Electrical Installation
3-4.9 GENII MZS REM Multi Zone Station Module
The GENII MZS REM Multi Zone Station Module (Figure 3-13) is powered by 24VAC ±10% @ 50/60Hz. Power
Consumption is 3VA maximum.
The GENII MZS REM mounts into a standard electrical wall plate. The only connections to the GENII MSZ
REM are 24VDC power and the RS485 Comms link. Locations of electrical terminals are shown in Figure 3-13,
which is a rear view of the module.
When all connections have been made, protect the module from dirt and moisture by covering it with plastic
but do not mount the module in the wall plate until commissioning is completed. This is to allow addresses
to be set as part of the commissioning process.
END OF
CABLE
JUMPER
RS485
COMMS
CONNECTIONS
POWER
Figure 3-13: GENII MZS REM Multizone Station Module