Voltage check, innotech repeater, E 5-21, Figure – Innotech Genesis II Digital Controller (v5) User Manual
Page 123: As appr, Figure 5-21, Comms cables for port 2, Comms cables for port 1, Measurements made with earth wire connected

Page 123
Genesis II Installation Instructions
© Mass Electronics Pty Ltd 2010
Chapter 5 – Network Installation
Comms Cables for Port 2
V
AC
V
DC
24V
1
2
Isolated from
internal circui t
Connected to
internal circui t
EARTH
L
N
E
Measurements Made
With Earth Wire
Connected
Comms Cables for Port 1
V
AC
V
DC
3.5V
1
2
Isolated from
internal circui t
Connected to
internal circui t
EARTH
L
N
E
Measure AC and DC
voltages: Should be
less than 3.5Vac and
between +10Vdc and
-5Vdc.
Measure AC and DC
voltages: Should be
less than 24Vac and
between +33Vdc and
-33Vdc.
Figure 5-21: Voltage Check, Innotech Repeater