beautypg.com

Networking and earthing the innotech repeater ir12, E 5-13, Building a building b – Innotech Genesis II Digital Controller (v5) User Manual

Page 115

background image

Page 115

Genesis II Installation Instructions

© Mass Electronics Pty Ltd 2010

Chapter 5 – Network Installation

Neither the Innotech Repeater IR11 or IR12 have a separate earth terminal as it is a 24VAC powered

device; however, the 24 V supply must be earthed on the 0 V side for safety and to make use of the

Soft Earth feature.

The IR12 is the current dual channel and dual baud rate repeater. The IR11 is the current single

channel dual baud rate repeater. The IR12 and IR11 are fully isolated and both Port 1 and Port 2

offer the same level of protection. That means that both Ports 1 & 2 can be used for the remote site

connection.

Building A

Building B

Hard Earth

Port 1

Port 2

Soft Earth

Hard Earth

5-3.5.5 GENII MPI Modem Printer Interface

The GENII MPI Modem and Printer Interface can be used with both the Genesis II Direct Digital

Controller and MPCII Mid Points Controller.

The MPI is supplied with a double insulated plug pack, which isolates the MPI power supply from the

electrical earth. However, when a printer or PC is connected to the MPI it will be connected to the

electrical earth via the printer and/or PC cables. See

Figure 5-14

.

The Comms is connected to the MPI via the RJ11 socket on the rear of the MPI. The top portion

of

Figure 5-14

shows the socket connections and the cable as supplied. The standard order for

conductor colours is shown, but they may change and, therefore, should always be checked before

connecting.

To isolate the screen of the Comms cabling from electrical earth at a non-isolated MPI, do not

connect the two GND conductors of the flat MPI cable to the screen(s) of the Comms cables at the

wall connection. This is not an isolated connection for the data conductors.

To provide isolation for the data conductors, an MPI fitted with RS485 isolation ICs must be used.

The two GND conductors should be connected to the screen(s) of the Comms cable when an isolated

MPI is used. Connecting the screen(s) of the Comms cable(s) completes the internal overvoltage

protection on the MPI data connections.

The earth on the Innotech Repeater IR12 must be connected to the soft earth terminal.

NOTE

Refer to Figure 5-13 below for a common networking example, using the Innotech Repeater IR12

Module.

Figure 5-13:  Networking and Earthing the Innotech Repeater IR12