4.14 genii mp405 rem multipoint module, Genii mp405 rem multipoint module, E 3-18 – Innotech Genesis II Digital Controller (v5) User Manual
Page 64: Mp405, Important

Genesis II Installation Instructions
Page 64
© Mass Electronics Pty Ltd 2010
Edition 2.0 dated 06/12/2013
3-4.14 GENII MP405 REM Multipoint Module
The Innotech GENII MP405 REM Multipoint Module is a remote expansion device that has both input
and output expansion capabilities. The GENII MP405 REM provides relay outputs for distributed
control, digital inputs for status detection and Thermistor inputs for temperature measurement.
The GENII MP405 REM (Figure 3-18) is powered by 24VAC ±10% @ 50/60 Hz, or powered by 24VDC
±15%. Power Consumption is 4VA maximum.
Inputs:
• 10 kΩ thermistor temperature sensor.
• 4 x 24VAC or DC Isolated switched contact digital inputs.
Outputs:
• 5 x 24VAC or DC Relay Outputs, Normally Open contacts. Rated at 16 Amp Resistive, 6 Amp
Inductive.
The RS485 Comms connection block is in the lower-left section of the module (as illustrated above)
and the End of Cable Jumper is next to it.
NOTE:
ALL OUTPUT RELAYS:-
Rated at :
16Amp R esistive
6Amp Inductive
Com = Common Contact
NO = Normally Open Contact
24V AC /DC
24V AC or DC Supply
C
O
N
TR
O
L
S
Y
S
TE
M
S
A
U
S
TR
A
L
IA
®
0V AC or DC Supply
MP405
(Voltage Free Contacts by other)
DIGI TA L I NPUT S
+24V
0V
DI#+
DI#-
NOTE:
ALL DIGITAL INPUTS:-
Ra ted at :
24V (AC or DC)
(Voltage Free Contacts by other)
TYPICAL DIGI TA L I NPUTS
SENSOR
C+
C-
S2
S1
Comms
+24V
0V
EARTH
D
I 4
D
I 1
D
I 2
D
I 3
+
-
Comms
Jumpe
rs
A2
A1
A0
TERM
SHLD2
SHLD1
TH2
TH1
+
-
+
-
+
-
+
-
Com
NO
D
O
1
D
O
2
D
O
3
D
O
4
0
V
24
V
Com
NO
Com
NO
Com
NO
D
O
5
Com
NO
E
D
I 4
D
I 1
D
I 2
D
I 3
+
-
Comms
Jumpe
rs
A2
A1
A0
EOL
SHLD2
SHLD1
TH2
TH1
+
-
+
-
+
-
+
-
Figure 3-18: GENII MP405 REM Multipoint Module
The unit must be powered down before jumpers are altered. Anti-static precautions should be taken when changing
addresses or adding or removing cabling from the terminals.
IMPORTANT