beautypg.com

4.16 genii mp423 rem multipoint module, Genii mp423 rem multipoint module, E 3-20 – Innotech Genesis II Digital Controller (v5) User Manual

Page 68

background image

Genesis II Installation Instructions

Page 68

© Mass Electronics Pty Ltd 2010

Edition 2.0 dated 06/12/2013

3-4.16 GENII MP423 REM Multipoint Module

The Innotech GENII MP423 REM Multipoint Module is a remote expansion device that has both input

and output expansion capabilities. The GENII MP423 REM provides relay outputs for distributed

control, digital inputs for status detection and Thermistor inputs for temperature measurement.

The GENII MP423 REM (Figure 3-20) is powered by 24VAC ±10% @ 50/60 Hz, or powered by 24VDC

±15%. Power Consumption is 4 VA maximum.

Inputs:

• 10 kΩ thermistor temperature sensor.

• 4 x 24VAC or DC Isolated switched contact digital inputs.

Outputs:

• 3 x 24VAC or DC Relay Outputs, Normally Open contacts. Rated at 16 Amp Resistive, 6 Amp

Inductive.

• 2 x Analogue Output, 0-10V DC ±0.05V into > 2 kΩ load.

The RS485 Comms connection block is in the lower-left section of the module (as illustrated above)

and the End of Cable Jumper is next to it.

The unit must be powered down before jumpers are altered. Anti-static precautions should be taken when changing

addresses or adding or removing cabling from the terminals.

IMPORTANT

Figure 3-20:  GENII MP423 REM Multipoint Module