beautypg.com

Genesis ii ddc analogue outputs – Innotech Genesis II Digital Controller (v5) User Manual

Page 41

background image

Page 41

Genesis II Installation Instructions

© Mass Electronics Pty Ltd 2010

Chapter 3 – Electrical Installation

Refer to Table 3-6 below for Analogue Output terminal numbers. There are 16 Analogue active signal

terminals (AO1 through AO16), one for each channel and eight return (Common) terminals. The fewer

number of Common terminals is intended to reduce the overall number of terminals.

Cable screening may be terminated into the Screens Terminals (20 and 21), space permitting.

Alternatively, all cable screens can be combined by soldering within the slotted cable-routing ducts

with a common 1mm

2

earth lead connected to Terminals 20 or 21.

Terminal

Signal

Terminal

Signal

66

AO1

78

AO5

67

AO2

79

AO6

68

AO3

80

AO7

69

AO4

81

AO8

70

Common

82

Common

71

Common

83

Common

72

Common

84

Common

73

Common

85

Common

74

AO9

86

AO13

75

AO10

87

AO14

76

AO11

88

AO15

77

AO12

89

AO16

Table 3-6: 