C Physical and Environmental Specifications

Table C-1

provides temperature and airflow information for minimum, typical, and maximum

configurations for the HP 9000 rp3410 and rp3440 servers. It also lists the server and rack weights
and dimensions.

Table C-1 Physical and Environmental Specifications

Overall Server (W x D
x H)

Weight

Condition

Airflow, at
Maximum
Ambient degrees
C

1

Airflow, Nominal

Typical
Heat
Release

Pede-stal

Rack

Pede-
stal

Rack

Server
Alone

100-250
VAC

W: 11.6 in
(29.5 cm)
D: 26.6 in
(67.5 cm)

H: 19.5 in
(49.4 cm)

W: 19.0 in
(48.3 cm)
D: 26.8 in
(67.9 cm)

H: 3.4 in
(8.6 cm)

56.3 lbs
(25.5
kg)

49.0 lbs
(22.2 kg)

38.6 lbs
(17.5 kg)

115.94

m3/hr

68.2

CFM

98.3

m3/hr

57.8

CFM

341 Watts

Min.
Config.

536 Watts

Max.
Config.

426 Watts

Typical
Config.

One dual-core CPU, one power supply, 2 GB DIMM,
zero DVD, three HDDs.

Min./
Config.

Airflow cooling scheme (front to rear)

ASHRAE
Class 1

Two dual-core CPUs, one power supply, 32 GB
DIMM, one DVD, three HDDs, one graphics card,
one SCSI card.

Max.
Config.

One dual-core CPU, one power supply, 6 GB DIMM,
one DVD, three HDDs, one graphics card, one SCSI
card.

Typical
Config.

1

Derate maximum dry bulb temperature 1 degree per 300 meters above 900 meters.

205