6C105/6C107 and its installed modules is split 50/50 between the supplies (+/- 5%). The
Power Redundancy field displays whether or not the chassis is currently configured for
load sharing and power redundancy. Possible values are:

Available (Green) — Two 6C205-01 or 6C207-01 power supply modules are installed
in the 6C105/6C107 chassis.

Not Available (Yellow) — Only a single 6C205-01 or 6C207-01 power supply module
is installed in the 6C105/6C107 chassis. Note that when only a single power supply
module is installed, it must always be in power slot 1 (PS1).

PS #1/#2 Status

Indicates the state of any power supplies installed in the 6C105/6C107 Chassis. Possible
states returned are:

Not Available (Yellow) — No response has been returned from the device regarding
the power supplies.

Normal (Green) — A power supply is installed and operating in the associated power
slot.

Fault (Red) — The power supply in the associated power slot is not operational.

Not Installed (Blue) — The indicated power slot is not occupied by a power supply.

Fan Tray Status

The 6C105/6C107 supports a single, removable fan tray that has four fans. The tray is hot
swappable, so it can be removed without powering down the chassis. This field indicates
the status of the 6C105/6C107 Fan Tray:

Not Available (Yellow) — No response has been returned regarding the fan tray.

Normal (Green) — A fan tray is installed and operational.

Fault (Red) — One or more fans in the tray have failed.

Not Installed (Blue) — The fan tray slot is not occupied. The chassis is in danger of
overheating if it continues to run without the fan tray installed.