beautypg.com

ProSoft Technology 5204SE-MNET-PDPMV1 User Manual

Page 93

background image

Procedures 5204SE-MNET-PDPMV1

♦ ProLinx Gateway

User Manual

Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master


ProSoft Technology, Inc.

Page 93 of 235

December 22, 2009

3.7.7 Verify Communication between the Quantum Processor and

the Gateway

In this step, you will verify that the processor and the gateway are communicating
with each other over the Modbus TCP/IP Ethernet network. The sample project
includes an animation table called MNETDPV1_Table. When the processor is in
RUN

mode and communicating with the gateway, the values in this animation

table are updated whenever you trigger a GetModuleStatus read message to
request general gateway status from the gateway.

To verify communication between the processor and the gateway:

1 Place the processor in R

UN

mode, if you have not already done so.

2 In the Unity Pro Project Browser pane, click [+] to open the A

NIMATION

T

ABLES

tree, and then double-click MNETDPV1_T

ABLE

.

3 In the MNETDPV1_Table, you will see three main variables which can be

expanded to see many more sub-variables.

4 Look for the variable, MNETDPV1_StatIn. Click the [+] next to it to open it

and see all the sub-variables. These will include configuration information and
version/revision information, which will remain static, as well as program scan
counters, input/output update counters, request/response counters, and
others variables that should change whenever you trigger a status calls.