Slot Number and Slot Index

Used in the slave to address the desired data block.

Length

This parameter specifies the number of bytes of the data block to read. If the
slave data block length is less than requested, the length of the response will be
the actual length of the data block. If the slave data block is greater or equal, the
response will contain the same amount of data.

The slave may answer with an error response if data access is not allowed.

Data [1 … n]

Returned data.

Fault Information and Extended Fault Information

If "Invalid Other" is returned in the Acyclic Message Status Word in the header of
the response, information about the fault can be found here.

"Fault Information"

"Extended Fault Information" Contents

0001h

Address out of range

-

000Ah

Failed to execute request

000Bh

Remote station failure

Refer to Return Codes (page 219).

0010h

Remote station DP-V1 failure

Function_Number

0011h

Length out of range (>240 bytes)

-

0012h

Slave does not support DP-V1

-

0013h

Slave not active or not present in
configuration

-

00FEh

Command not possible in "Class 2-
Only" mode

-

00FFh

Module offline (not initialized or no
valid database)

-

Error Decode, Error Code 1 and Error Code 2

If "Fault Information" contains error code 0010h, refer to the slave device
manufacturer's documentation, or the EN50170 (DP-V1) protocol specification.