ProSoft Technology 5204SE-MNET-PDPMV1 User Manual
Page 29

Procedures 5204SE-MNET-PDPMV1
♦ ProLinx Gateway
User Manual
Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master
ProSoft Technology, Inc.
Page 29 of 235
December 22, 2009
6 Double click the S
LAVE
icon to view the Slave properties dialog.
ProSoft Configuration Builder automatically assigns a PROFIBUS address to
each new slave. The slave address assignment begins at address 3 for the
first slave added to the network (addresses 0, 1, and 2 are reserved for use
with PROFIBUS Masters), and is incremented by 1 for each new slave added
to the network. You may, however, assign any address, 0-125 to any Master
or slave node as long as you do not assign the same address to more than
one device. You can change the address in the C
OMMON
tab of the Slave
properties dialog box. ProSoft Configuration Builder will not allow you to
assign a PROFIBUS address that is already in use by another device on this
network.
Leave the remaining settings unchanged for now, and click OK
to close the
Slave properties dialog box.
7 Repeat steps 2 through 6 for all slaves you intend to place on the network.
8 When you are finished adding slaves, open the P
ROJECT
menu and choose
E
XIT
.
Click Y
ES
to save the project and return to the PROFIBUS Master Setup
dialog box.