ProSoft Technology 5204SE-MNET-PDPMV1 User Manual
Page 200

5204SE-MNET-PDPMV1 ♦ ProLinx Gateway
Reference
Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master
User Manual
Page 200 of 235
ProSoft Technology, Inc.
December 22, 2009
4.6.4 Get Slave Configuration Message Structure
Parameter Description
Command Initiator
Application
Command Name
FB_APPL_GET_SLAVE_CONFIG
Command Number
0005h
Fragmented No
Extended Header Data
Fault information may be returned in the header of the response.
Command and Response Layout: Get Slave Configuration
Command
Response
Message ID
(ID)
(ID)
Acyclic Message Status
Word
4002h
0002h
Command
0005h
0005h
Get Slave Configuration
Data size
0000h
(Size of data)
Number of identifier bytes
(n)
Frame count
0001h
0001h
Frame number
0001h
0001h
Offset high
0000h
0000h
Offset low
0000h
0000h
Extended word 1
Slave
Address
-
Slave
Address
-
Extended word 2
-
-
Extended word 3
-
-
Extended word 4
-
-
Extended word 5
-
Error Code 1 Error Code 2
Extended word 6
-
Error Code 3 Error Code 4
Extended word 7
-
Return Code
Extended word 8
-
Fault Information
Identifier byte 1
Response data word 1
Identifier byte 2
Response data word 2
Identifier byte 3
Response data word 3
... ...
Identifier byte n
Response data word n
Acyclic Message Status Word
Refer to Acyclic Message Status Word (page 218).
Slave Address
Range 0 to 125, specifies the slave from which to read the configuration.