ProSoft Technology 5204SE-MNET-PDPMV1 User Manual
Page 151

Reference 5204SE-MNET-PDPMV1
♦ ProLinx Gateway
User Manual
Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master
ProSoft Technology, Inc.
Page 151 of 235
December 22, 2009
Variable Name Size/Type Description
Out -
WriteCyclicData
1
Single-bit
Boolean
This is the bit your control and sequencing logic will use to
trigger a cyclic write message. Set this bit to one (1) whenever
no other messages are active and when you want to send
PROFIBUS cyclic slave output data.
Out -
RegisterCount
1
16-bit integer
Will hold the total number of 16-bit register words of
PROFIBUS cyclic output data that need to be written. This
value will be the same as what you entered in the PCB
configuration for the [PROFIBUS
M
ASTER
DPV1]
O
UTPUT
D
ATA
S
IZE
parameter.
Out -
IPAddress[ ]
4-element
16-bit Integer
Array
Each of the four integer elements holds one octet of the
message destination device's IP Address. For this
application, it will be the the ProLinx gateway's Ethernet port
address.
Out - Routing
Register
1
16-bit Integer
Default value for Quantum processors with built-in Ethernet
port is 254 (16#FE00 hex)
For details, see "MBP_MSTR, Ethernet (Quantum) - Control
Block for TCP/IP Ethernet" in Quantum Help Files, or
Quantum Communication Control and Data Buffer Variables
and DDTs (page 137)
In -
WriteOperation
Active
1
Single-bit
Boolean
The DFB will set this bit when the Modbus TCP/IP message
has been initiated and is being processed.
In -
WriteOperation
Error
1
Single-bit
Boolean
The DFB will set this bit when the Modbus TCP/IP response is
successfully received and the PROFIBUS cyclic input data
variables have been updated.
In -
WriteOperation
Success
1
Single-bit
Boolean
The DFB will set this bit when the Modbus TCP/IP response is
successfully received and the PROFIBUS cyclic output data
variables have been updated.