Reference 5204SE-MNET-PDPMV1

♦ ProLinx Gateway

User Manual

Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master


ProSoft Technology, Inc.

Page 155 of 235

December 22, 2009

Variable Name

Size/Type Description

Out - GetModuleStatus

1

Single-bit
Boolean

This is the bit your control and sequencing logic will
use to trigger a message to get general gateway status
data. Set this bit to one (1) whenever no other
messages are active and when you want to update the
StatInF variable table.

Out - IPAddress[ ]

4-element

16-bit
Integer
Array

Each of the four integer elements holds one octet of the
message destination device's IP Address. For this
application, it will be the the ProLinx gateway's
Ethernet port address.

Out - RoutingRegister

1

16-bit
Integer

Default value for Quantum processors with built-in
Ethernet port is 254 (16#FE00 hex)

For details, see "MBP_MSTR, Ethernet (Quantum) -
Control Block for TCP/IP Ethernet" in Quantum Help
Files, or Quantum Communication Control and Data
Buffer Variables and DDTs (page 137)

In - StatusOperationActive

1

Single-bit
Boolean

The DFB will set this bit when the Modbus TCP/IP
message has been initiated and is being processed.

In - StatusOperationError

1

Single-bit
Boolean

The DFB will set this bit when the Modbus TCP/IP
response is not successfully received. When this bit is
set, it indicates your control and sequencing logic
should retry the command.

In - StatusOperationSuccess 1

Single-bit
Boolean

The DFB will set this bit when the Modbus TCP/IP
response is successfully received and the PROFIBUS
cyclic input data variables have been updated.

In - Fault

1

16-bit
Integer

If "Invalid other" is returned in the Acyclic Message
Status Word in the header of the response, information
about the fault can be found here. Refer to Acyclic
Message Status Word (page 218)

0001h: Address out of range.

000Ah: Failed to execute request. Refer to Return
Codes (page 219) for additional information.

000Bh: Remote station failure. Refer to Return Codes
(page 219) for additional information.

00FFh: gateway not initialized.

In - ReturnCode

1

16-bit
Integer

Refer to Return Codes (page 219) for additional
information.