Reference 5204SE-MNET-PDPMV1

♦ ProLinx Gateway

User Manual

Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master


ProSoft Technology, Inc.

Page 127 of 235

December 22, 2009

Variable Name

Size/Type Description

Out - Timeout

1

16-bit Integer

Used to hold the amount of time in milliseconds to wait for a
response to the Modbus TCP/IP command before assuming
a communication error has occurred and setting the In-
MessageError status bit

Out -
SetSlaveMode

1

Single-Bit
Boolean

This is the bit your control and sequencing logic will use to
trigger a message to tell the PROFIBUS Master to change
the operating mode of a single slave or group of slaves. Set
this bit to one (1) whenever no other messages are active
and you want to send this acyclic message.

Out - SlaveAddress 1

8-bit Byte

Valid entries: 0-125, 127

If you enter a value from 0 to 125, the acyclic message will
affect only the one slave device at this address.

If you enter a value of 127, the acyclic message will affect a
group of slaves, specified by the Out-GroupSelect
parameter.

Out - GroupSelect

1

8-bit Byte

For details on how to set this parameter, see Set Slave
Mode Message Structure (page 206)

Out -
CommandControl

1

8-bit Byte

For details on how the set this parameter, see Set Slave
Mode Message Structure (page 206)

Out - MailBoxData

Multi-variable
nested DDT

For details, see Modbus DDT (page 98)

In - MessageDone

1

Single-bit
Boolean

The DFB will set this bit when the Modbus TCP/IP response
is successfully received.

In - MessageError

1

Single-bit
Boolean

The DFB will set this bit when the Modbus TCP/IP response
is not successfully received. When this bit is set, it indicates
your control and sequencing logic should retry the
command.