ProSoft Technology 5204SE-MNET-PDPMV1 User Manual

Page 167

background image

Reference 5204SE-MNET-PDPMV1

♦ ProLinx Gateway

User Manual

Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master


ProSoft Technology, Inc.

Page 167 of 235

December 22, 2009

Variable Name

Size/Type Description

Out - GetLiveList

1

Single-Bit
Boolean

This is the bit your control and sequencing logic will use to
trigger a message to tell the PROFIBUS Master provide a
list of active slave nodes. Set this bit to one (1) whenever
no other messages are active and you want to send this
acyclic message.

Out - IPAddress[ ]

4-element

16-bit
Integer Array

Each of the four integer elements holds one octet of the
message destination device's IP Address. For this
application, it will be the the ProLinx gateway's Ethernet
port address.

Out - RoutingRegister

1

16-bit
Integer

Default value for Quantum processors with built-in
Ethernet port is 254 (16#FE00 hex)

For details, see "MBP_MSTR, Ethernet (Quantum) -
Control Block for TCP/IP Ethernet" in Quantum Help Files,
or Quantum Communication Control and Data Buffer
Variables and DDTs (page 137)

In - ListOperationActive 1

Single-bit
Boolean

The DFB will set this bit when the Modbus TCP/IP
message has been initiated and is being processed.

In - ListOperationError

1

Single-bit
Boolean

The DFB will set this bit when the Modbus TCP/IP
response is not successfully received. When this bit is set,
it indicates your control and sequencing logic should retry
the command.

In -
ListOperationSuccess

1

Single-bit
Boolean

The DFB will set this bit when the Modbus TCP/IP
response is successfully received and the PROFIBUS
cyclic input data variables have been updated.

In - StationsStatus[ ]

127 element

8-bit Byte
Array

Each byte will contain one of the following codes indicating
type of node present at that node address:

00h: Slave Station

01h: Master Station not yet ready for Token ring (station
physically attached to the bus but not configured or polling)

02h: Master Station ready to enter Token ring (station is
configured but not polling; there is not yet any Token
transmission)

03h: Master Station in Token Ring (Token transmission
through the station; station is fully operational)

04h: Station does not exist

In - Fault

1

16-bit
Integer

For details on Fault Codes, see Acyclic Message Status
Word (page 218).

In - Return Code

1

16-bit
Integer

For details, see Return Codes (page 219).