beautypg.com

ProSoft Technology 5204SE-MNET-PDPMV1 User Manual

Page 216

background image

5204SE-MNET-PDPMV1 ♦ ProLinx Gateway

Reference

Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master

User Manual


Page 216 of 235

ProSoft Technology, Inc.

December 22, 2009

4.6.11 Write Class 1 Acyclic Data Message Structure

Parameter Description

Command Initiator

Application

Command Name

FB_APPL_MSAC1_WRITE

Command Number

0021h

Fragmented No

Extended Header Data

Fault information may be returned in the header of the response.

Command and Response Layout: Acyclic Write

Command

Response

Message ID

(ID)

(ID)

Acyclic Message Status

Word

4002h

0002h

Command

0021h

0021h Acyclic

Write

Data size

(Size of data)

(Size of data)

Number of data bytes (n)

Frame count

0001h

0001h

Frame number

0001h

0001h

Offset high

0000h

0000h

Offset low

0000h

0000h

Extended word 1 Slave Addr. Slot Number Slave Addr. Slot Number
Extended word 2

Index

Length Index

Length

Extended word 3

-

-

Extended word 4

-

-

Extended word 5

-

Error

Decode-

Extended word 6

-

Error Code 1 Error Code 2

Extended word 7

-

Extended Fault information

Extended word 8

-

Fault Information

Message Data byte 1

Data 1

Data 1

Message Data byte 2

Data 2

Data 2

Message Data byte 3

Data 3

Data 3

... ...

...

Message Data byte n

Data n

Data n

Acyclic Message Status Word

Refer to Acyclic Message Status Word (page 218).

Slave Address

Station address of the slave responder.

Slot Number and Slot Index

Used in the slave to address the desired data block.