5204SE-MNET-PDPMV1 ♦ ProLinx Gateway

Reference

Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master

User Manual


Page 182 of 235

ProSoft Technology, Inc.

December 22, 2009

Variable Name

Size/Type

Description

In - Fault

1

16-bit Integer

If "Invalid other" is returned in the Acyclic Message
Status Word in the header of the response, information
about the fault can be found here. Refer to Acyclic
Message Status Word (page 218)

0001h: Address out of range.

000Ah: Failed to execute request. Refer to Return Codes
(page 219) for additional information.

000Bh: Remote station failure. Refer to Return Codes
(page 219) for additional information.

00FFh: gateway not initialized.

In - SetAddressData

200-element
8-bit Byte
Array

Additional message data that may be returned by the
slave

In - SetSlaveAddActive

1

Single-bit
Boolean

The DFB will set this bit when the Modbus TCP/IP
message has been initiated and is being processed.

In - SetSlaveAddError

1

Single-bit
Boolean

The DFB will set this bit when the Modbus TCP/IP
response is not successfully received. When this bit is
set, it indicates your control and sequencing logic should
retry the command.

In -
SetSlaveAddSuccess

1

Single-bit
Boolean

The DFB will set this bit when the Modbus TCP/IP
response is successfully received and the PROFIBUS
cyclic input data variables have been updated.