Page 211

background image

Reference 5204SE-MNET-PDPMV1

♦ ProLinx Gateway

User Manual

Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master


ProSoft Technology, Inc.

Page 211 of 235

December 22, 2009

New Slave Address

Range 0 to 125

Specifies the new address of the slave.

Slave Ident Number

Ident number for the slave, which address should be altered.

No_Add_Change

This parameter specifies whether it is allowed to change the slave address again
at a later stage. If this is not allowed, then it is only possible to change the
address with this function after initial reset. After the initial reset, the slave takes
the default address 126.

00h

Change of address is still possible at a later stage

01h - FFh

Change of address is only possible after the initial address (the

default address = 126)

Error Code [1 ... 4]

If 'Return Code' equals 8030h ('Negative indication from lower layer'), status
values according to the DP-specification is available in 'Error Code 1'. Error
Codes 2 to 4 are reserved.

(See Return Codes (page 219) and Error Codes)

Fault Information and Extended Fault Information

"Fault Information" Contents

"Extended Fault Information" Contents

0001h

Current Slave Address out of range

-

0002h

New Slave Address out of range

-

000Ah

Failed to send Global Control
request

For additional fault information, see Return
Codes (page 219)

000Bh

Remote Station Failure

For additional fault information, see Return
Codes (page 219)

00FFh

Module offline

(not initialized or no valid database)

Slave Data

With this parameter it is possible to deliver user specific data. The data is stored
in the slave if possible (EEPROM, FLASH, etc.)