ProSoft Technology 5204SE-MNET-PDPMV1 User Manual
Page 194

5204SE-MNET-PDPMV1 ♦ ProLinx Gateway
Reference
Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master
User Manual
Page 194 of 235
ProSoft Technology, Inc.
December 22, 2009
4.6
PROFIBUS Acyclic Telegram (Message) Block Structures
4.6.1 Set Operating Mode Message Structure
Parameter Description
Command Initiator
Application
Command Name
FB_APPL_SET_OPERATION_MODE
Command Number
0002h
Fragmented No
Extended Header Data
Fault information may be returned in the header of the response.
Command and Response Layout: Set Operating Mode
Command
Response
Message ID
(ID)
(ID)
Acyclic Message Status
Word
4002h
0002h
Command
0002h
0002h
Set Operation Mode
Data size
0000h
0000h
Frame count
0001h
0001h
Frame number
0001h
0001h
Offset high
0000h
0000h
Offset low
0000h
0000h
Extended word 1 Req. Mode
Conf. Req
Act. Mode
Conf. Req
Extended word 2
-
-
Extended word 3
-
-
Extended word 4
-
-
Extended word 5
-
-
Extended word 6
-
-
Extended word 7
-
Appl. Specific Error Code
Extended word 8
-
Fault Information
Mode
40h: STOP
80h: CLEAR
C0h: OPERATE
Conf. Req.
00h: Confirmation is not required
01h: Confirmation required. All confirmations are automatically sent by the
master, the user is not required to send a confirmation message.