ProSoft Technology 5204SE-MNET-PDPMV1 User Manual
Page 67

Procedures 5204SE-MNET-PDPMV1
♦ ProLinx Gateway
User Manual
Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master
ProSoft Technology, Inc.
Page 67 of 235
December 22, 2009
3.6.4 Import the M340 Variables (.XSY file)
The Application Communication Logic functions of ProSoft Configuration Builder
(PCB) also create a list of variables and variable structures customized to the
particular PROFIBUS DP-V1 Master configuration you created. These variables
are contained in the "{ProjectName}.XSY" file you exported in Export the Unity
Pro v 4.0 Logic Support Files (page 47).
The .XSY file contains all the cyclic input and output variables configured by the
PCB master configuration software. This file includes gateway status data and
will also include slave diagnostics data if the S
LAVE
D
IAGNOSTICS
parameter was
set to Yes.
To import the Variables:
1 In the Project Browser, select V
ARIABLES
&
FB
I
NSTANCES
, and click the right
mouse button to open a shortcut menu. On the shortcut menu, choose
I
MPORT
.
2 In the F
ILES OF
T
YPE
: dropdown list, choose
D
ATA
E
XCHANGE
F
ILE
(*.XSY).
Select the .xsy file created when you exported the processor files from PCB
(page 47) and then click I
MPORT
.
3 If you see an Import Trouble Report window, click R
EPLACE
A
LL
, then click
OK.
At this point, the DDTs, DFBs, and Variables have been imported to the
application.