ProSoft Technology 5204SE-MNET-PDPMV1 User Manual
Page 217

Reference 5204SE-MNET-PDPMV1
♦ ProLinx Gateway
User Manual
Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master
ProSoft Technology, Inc.
Page 217 of 235
December 22, 2009
Length
This parameter specifies the number of bytes to write. If the destination data
block size is less than requested, the response will contain an error message. If
the data block length is greater than or equal to the requested length, the
response contains the number of bytes that have been written. The slave may
answer with an error response if data access is not allowed.
Data [1 … n]
Data that should be written.
Fault Information and Extended Fault Information
If "Invalid Other" is returned in the Acyclic Message Status Word in the header of
the response, information about the fault can be found here:
"Fault Information"
"Extended Fault Information" Contents
0100h
Address out of range
-
0A00h
Failed to execute request
0B00h
Remote station failure
Refer to Return Codes (page 219).
1000h
Remote station DP-V1 failure
Function_Number
1100h
Length out of range (>240 bytes)
-
1200h
Slave does not support DP-V1
-
1300h
Slave not active or not present in
configuration
-
FE00h
Command not possible in "Class 2-
Only" mode
-
FF00h
Module offline (not initialized or no
valid database)
-
Error Decode, Error Code 1, and Error Code 2
If "Fault Information" contains error code 1000h, more information according to
the DP-V1 specification can be found here.