Mailbox Messaging

PDPMV1 ♦ ProLinx Gateway

Protocol Manual

PROFIBUS DPV1 Master

Page 92 of 157

ProSoft Technology, Inc.

March 23, 2011

Slave Address
Station address of the slave responder.

Slot Number and Slot Index
Used in the slave to address the desired data block.

Length
This parameter specifies the number of bytes of the data block to read. If the
server data block length is less than requested, the length of the response will be
the actual length of the data block. If the server data block is greater or equal, the
response will contain the same amount of data.
The slave may answer with an error response if data access is not allowed.

Data [1 … n]
Returned data.

Fault Information and Extended Fault Information
If "Invalid Other" is returned in the Acyclic Message Status Word in the header of
the response, information about the fault can be found here.

"Fault Information"

"Extended Fault Information" Contents

0100h

Address out of range

-

0A00h

Failed to execute request

Refer to Return Codes (page 100).

0B00h

Remote station failure

1000h

Remote station DPV1 failure

Function_Number

1100h

Length out of range (>240 bytes)

-

1200h

Slave does not support DPV1

-

1300h

Slave not active or not present in
configuration

-

FE00h

Command not possible in "Class 2-
Only" mode

-

FF00h

Module offline (not initialized or no
valid database)

-

Error Decode, Error Code 1 and Error Code 2
If "Fault Information" contains error code 1000h, more information according to
the DPV1 specification can be found here.