ProSoft Technology 5204-DFNT-PDPMV1 User Manual
Page 92
Mailbox Messaging
PDPMV1 ♦ ProLinx Gateway
Protocol Manual
PROFIBUS DPV1 Master
Page 92 of 157
ProSoft Technology, Inc.
March 23, 2011
Slave Address
Station address of the slave responder.
Slot Number and Slot Index
Used in the slave to address the desired data block.
Length
This parameter specifies the number of bytes of the data block to read. If the
server data block length is less than requested, the length of the response will be
the actual length of the data block. If the server data block is greater or equal, the
response will contain the same amount of data.
The slave may answer with an error response if data access is not allowed.
Data [1 … n]
Returned data.
Fault Information and Extended Fault Information
If "Invalid Other" is returned in the Acyclic Message Status Word in the header of
the response, information about the fault can be found here.
"Fault Information"
"Extended Fault Information" Contents
0100h
Address out of range
-
0A00h
Failed to execute request
Refer to Return Codes (page 100).
0B00h
Remote station failure
1000h
Remote station DPV1 failure
Function_Number
1100h
Length out of range (>240 bytes)
-
1200h
Slave does not support DPV1
-
1300h
Slave not active or not present in
configuration
-
FE00h
Command not possible in "Class 2-
Only" mode
-
FF00h
Module offline (not initialized or no
valid database)
-
Error Decode, Error Code 1 and Error Code 2
If "Fault Information" contains error code 1000h, more information according to
the DPV1 specification can be found here.