3.2.4 Mailbox Message: Get Slave Configuration

This command reads the actual configuration (identifier bytes) of a specified
slave.

Note: The response data size depends on the actual slave implementation. Range 6 to 244.

Parameter

Description

Command Initiator

Application

Command Name

GET SLAVE CONFIGURATION

Command Number

0500h

Fragmented

No

Extended Header Data

Fault information may be returned in the header of the response.

Command and Response Layout: Get Slave Configuration

Command

Response

Message ID

(ID)

(ID)

Acyclic Message Status

Word

4002h

0002h

Command

0005h

0005h

Get Slave Configuration

Data size

0000h

(Size of data)

Number of identifier bytes
(n)

Frame count

0001h

0001h

Frame number

0001h

0001h

Offset high

0000h

0000h

Offset low

0000h

0000h

Extended word 1

Slave

Address

Slave

Address

Extended word 2

-

-

Extended word 3

-

-

Extended word 4

-

-

Extended word 5

-

Error Code 1 Error Code 2

Extended word 6

-

Error Code 3 Error Code 4

Extended word 7

-

Return Code

Extended word 8

-

Fault Information

Identifier byte 1

Response data word 1

Identifier byte 2

Response data word 2

Identifier byte 3

Response data word 3

...

...

Identifier byte n

Response data word n