3.3.4 DP-V1 Error Codes

Possible error codes in Message Data word "Return Code".

Return Code

Name

Meaning

0003h

DPMC_ERR_M_MEM_ALLOC

Internal memory allocation error

0004h

DPMC_ERR_M_L2_REQ

Unknown opcode in the configuration

0005h

DPMC_ERR_M_INVALID_PAR

Invalid parameter in user request

0007h

DPMC_ERR_M_NOT_IN_DATA

Slave is not in DataExchange (thus no DP-V1 request can
exist)

0012h

DPMC_ERR_M_REQ_ACTIVE

A request is already active

0018h

DPMC_ERR_M_NOT_ALLOWED

Internal DPMC module not initialized correctly

0021h

DPMC_ERR_M_CLOSED

Internal DPMC instance no longer exists

0022h

DPMC_ERR_M_STOPPED

Internal DPMC instance has already been stopped

0023h

DPMC_ERR_M_STARTED

Internal DPMC instance has already been started

0024h

DPMC_ERR_M_STATE_UNKNOWN

Internal DPMC instance has entered an undefined state

002Fh

DPMC_ERR_M_SLAVE_NOT_FOUND

Slave does not respond

0031h

DPMC_ERR_M_TIMEOUT

Active request terminated with timeout

0034h

DPMC_ERR_M_INVALID_LEN

Invalid length in user request

0035h

DPMC_ERR_M_REQ_NEG

Negative indication from lower layer

0036h

DPMC_ERR_M_REQ_RE

Message frame format error in response

0037h

DPMC_ERR_M_REQ_WITHDRAW

Request was recalled

0038h

DPMC_ERR_M_REQ_NOT_FOUND

Associated request block not found

0040h

DPMC_ERR_M_MM_FE

Format error in request frame

0041h

DPMC_ERR_M_MM_NI

Function not implemented

0042h

DPMC_ERR_M_MM_AD

Access denied

0043h

DPMC_ERR_M_MM_EA

Area too large

0044h

DPMC_ERR_M_MM_LE

Data block length too large

0045h

DPMC_ERR_M_MM_RE

Format error in response frame

0046h

DPMC_ERR_M_MM_IP

Invalid parameter

0047h

DPMC_ERR_M_MM_SC

Sequence conflict

0048h

DPMC_ERR_M_MM_SE

Sequence error

0049h

DPMC_ERR_M_MM_NE

Area non-existent

004Ah

DPMC_ERR_M_MM_DI

Data incomplete or incorrect

004Bh

DPMC_ERR_M_MM_NC

Master parameter set not compatible

004Ch

DPMC_ERR_M_S7_XA

004Dh

DPMC_ERR_M_S7_XR

PROFIBUS error for DP-V1 (NRS-PDU received)

004Eh

DPMC_ERR_M_S7_XW

This manual is related to the following products: