ProSoft Technology 5204-DFNT-PDPMV1 User Manual
Page 103
PDPMV1 ♦ ProLinx Gateway
Mailbox Messaging
PROFIBUS DPV1 Master
Protocol Manual
ProSoft Technology, Inc.
Page 103 of 157
March 23, 2011
3.3.5 Command Error Codes
Errors reported from the command list of the gateway require 8 bytes or 4 words
per command. If the first 7 bytes of the error are 0xFF, this is a gateway-
generated error as follows:
Value of Last Byte Error Definition
0x00
Too few parameters for command in command list section of configuration
file.
0x01
Invalid type value specified for command.
0x02
Invalid database offset specified for command.
0x03
Invalid swap type code specified for command.
0x04
Invalid database trigger address
0x05
Invalid database address and count combination
0x10
Invalid function code specified for command.
0xFF
Response timeout for command recognized.
Refer to Error Codes (page 101) for an explanation of other error codes.
The 8 bytes (4 words) represent the extended words 5 to 8 in response
messages.