Mailbox Messaging

PROFIBUS DPV1 Master

Protocol Manual

ProSoft Technology, Inc.

Page 103 of 157

March 23, 2011

3.3.5 Command Error Codes

Errors reported from the command list of the gateway require 8 bytes or 4 words
per command. If the first 7 bytes of the error are 0xFF, this is a gateway-
generated error as follows:

Value of Last Byte Error Definition

0x00

Too few parameters for command in command list section of configuration
file.

0x01

Invalid type value specified for command.

0x02

Invalid database offset specified for command.

0x03

Invalid swap type code specified for command.

0x04

Invalid database trigger address

0x05

Invalid database address and count combination

0x10

Invalid function code specified for command.

0xFF

Response timeout for command recognized.


Refer to Error Codes (page 101) for an explanation of other error codes.
The 8 bytes (4 words) represent the extended words 5 to 8 in response