ProSoft Technology 5204-DFNT-PDPMV1 User Manual
Page 108
Diagnostics and Troubleshooting
PDPMV1 ♦ ProLinx Gateway
Protocol Manual
PROFIBUS DPV1 Master
Page 108 of 157
ProSoft Technology, Inc.
March 23, 2011
4.3
PROFIBUS DP-V1 (PDPMV1 Driver) Master LED Indicators
The LEDs indicate the gateway’s operating status.
PROFIBUS Master Status LEDs
o
COM STAT
o
DBASE STAT
o
MAST STAT
o
TKN HOLD
4.3.1 PROFIBUS Master Indicators
LED
State
Description
TKN HLD
GREEN
The gateway has the token
OFF
The gateway does not have the token
DBASE STAT GREEN
Database OK
GREEN-Flashing
Database download in progress
RED
Invalid database
OFF
No databases have been downloaded
MSTR STAT
GREEN
Operating mode
GREEN-Flashing
Clear mode
RED
Stop mode
OFF
Offline
COM STAT
GREEN
Data exchange with all configured slaves
GREEN-Flashing
Data exchange with at least one configured slave but not all configured slaves
RED
Bus control error (possible bus short circuit or configuration error)
OFF
No data exchange with any configured slave
ALL LEDs
RED
Fatal error