beautypg.com

ProSoft Technology 5204-DFNT-PDPMV1 User Manual

Page 70

background image

Configuration

PDPMV1 ♦ ProLinx Gateway

Protocol Manual

PROFIBUS DPV1 Master

Page 70 of 157

ProSoft Technology, Inc.

March 23, 2011

To view or print the ProLinx Memory Map

1 In the Master Setup dialog box, click the S

HOW

PLX

M

EMORY

M

AP

button,

near the bottom of the window. This action opens ProLinx Memory Map
window.

2 Notice that there are buttons in the Display area of the dialog box to show

inputs and outputs. These input and output maps correspond to the input and
output data you configured for the PROFIBUS slaves (page 53). Notice also
that there are check boxes to display slot numbers and PROFIBUS
addresses.

3 Click P

RINT

to print the input and output maps for reference. Note that you

must do this for both input and output maps.

4 When you have finished printing the ProLinx memory maps, click OK to close

the dialog box. Click OK again to close the Master Setup dialog box.

5 Keep the printed memory maps available so you can refer to them when you

configure the sample ladder logic in RSLogix. The sample ladder logic
contains input and output arrays that must be cross-referenced with the
variables.

The next step is to download the project to the ProLinx gateway.

This manual is related to the following products: